OUTBACK FLEXware1000
The FLEXware 1000 system architecture is capable of supporting up to four OutBack FX Series Inverter/Chargers, four OutBack charge controllers, and all the required AC and DC components and wiring. Utilizing a compact design, FLEXware 1000 AC and DC enclosures accommodate all of the essential protective devices with lots of room for additional breakers and large cable connections and can be mounted either vertically or horizontially.
Model: FW1000-DC
DC enclosure which mounts at the DC side of three or four FX Series Inverter/Chargers. Supports eight terminal bus bars (not including GBB) and up to three shunt assemblies (depending on configuration).
Includes: Ground bus bar, 1000 Amp DC shunt assembly, positive bus, breaker mounting hardware, enclosure mounting hardware, two FW-SBUS and one FLEXware 1000 breaker bus.
Model
|
Unit Dimensions(H x W x D)
|
Shipping Dimensions(H x W x L)
|
Shipping Weight
|
Enclosure Type
|
FW1000-DC | 38.5 x 11.4 x 12.1" (97.8 x 29 x 30.7 cm) |
14.5 x 13.6 x 40.6" (36.8 x 34.5 x 103.1 cm) |
21lbs. (9.1kg) | Type-1 indoor(IP30) |
Model: FW1000-AC
Description:AC enclosure which mounts at the AC side of three or four FX Series Inverter/Chargers. Supports eight terminal bus bars and one FW-X240. The FW1000 system utilizes two FW-MPs (mounting plates) and a set of the DCA and ACA conduit adapters for each inverter/charger. DC and AC breakers, Input-Output-Bypass Assemblies and all other additional components sold separately.
Includes: Ground bus bar, two DIN mounting brackets and FLEXware 1000
Model
|
Unit Dimensions(H x W x D)
|
Shipping Dimensions(H x W x L)
|
Shipping Weight
|
Enclosure Type
|
FW1000-AC | 38.5 x 11.4 x 12.1" (97.8 x 29 x 30.7 cm) |
14.5 x 13.6 x 40.6" (36.8 x 34.5 x 103.1 cm) |
21lbs. (9.1kg) | Type-1 indoor(IP30) |
• The FW1000 system utilizes one FW-MP mounting plate and a set of the DCA and ACA conduit adapters for each inverter/charger.
• DC and AC breakers, Input-Output-Bypass Assemblies and all other additional components sold separately.
Breaker Configuration
AC side:
The breaker configuration will hold up to thirty-two DIN mount
breakers (not included). The FW1000 has support for an optional
AC Input-Output-Bypass Assembly. AC breakers
are rated from 10-60 Amps of Amps of AC current.
DC Side:
Holds up to eleven 0.75" (19mm) wide breakers rated for 1-80
Amps of DC current, nine 1" (26mm)wide breakers rated for
100 or 125 Amps of DC current or six 1.5" (32mm) wide breakers
rated for 175 or 250 Amps of DC current.
FLEXware 1000 AC Input-Output-Bypass Assemblies Field installable kit for bypassing the AC input to the AC output for inverter maintainence or installation. Also provides over-current protection.
Model: FW-IOB-T-120/208VAC
Includes:Nine 60A 120VAC single pole DIN mount breakers, sliding bypass interlock plate, wire and hardware kit
System Rating
|
Bypass Breaker
|
Input Breaker
|
Output Breaker
|
Two Phase 120/208VAC 60 Amp 21.6 kW |
Three Poles @ 60 Amps 21.6 kW | Three Poles @ 60 Amps 21.6 kW | Three Poles @ 60 Amps 21.6 kW |
Model: FW-IOB-Q-120/240VAC
Includes:Eight 60A 120VAC single pole DIN mount breakers, two 60A 120VAC dual pole DIN mount breakers sliding bypass interlock plate, wire and hardware kit
System Rating
|
Bypass Breaker
|
Input Breaker
|
Output Breaker
|
Split Phase 120/240VAC 120 Amp 28.8 kW |
Four Poles @ 60 Amps 28.8 kW | Four Poles @ 60 Amps 28.8 kW | Four Poles @ 60 Amps 28.8 kW |