Skip to content
Model Number Sunny-Central-760CP
Peak Efficiency 98.600
CEC Weighted Efficiency 98.500
Weight (lbs) 3968.3
Height (in) 90.0
Width (in) 101.0
Depth (in) 38.0

SMA Sunny Central 760CP Inverter

SKU Sunny-Central-760CP

Economical

  • Optiprotect ensures maximum plant availability
  • Outdoor-rated enclosure allows for direct field deployment

Efficient

  • Full nominal power at ambient temperatures up to 50° C
  • 110% rated power at ambient temperatures up to 25° C

Flexible

  • Configurable DC voltage range
  • Optional: Extended input voltage range up to 1,100 V

Reliable

  • Safe and easy installation due to separate connection area
  • Powerful grid management functions (including LVRT)

The Sunny Central CP series maximizes project investment returns through innovative technology and time-saving features. Optiprotect integrates string failure detection into the inverter and centrally monitors up to 1,600 module strings without requiring conventional communication wiring in the field. The self-learning monitoring system significantly simplifies commissioning. Up to 32 motor-driven, adjustable DC inputs ensure maximum plant availability. And, thanks to its compact and weatherproof enclosure, the inverters can be loaded and transported with ease and set up almost anywhere.

SMA Sunny Island Solar Inverters

 

 

 

Sunny Central Inverter Diagram

Input Data (DC)
Max. DC power (@ cos φ=1) 853 kW
Max. input voltage 1) 1000 V / 1100 V optional
MPP voltage range (@ 25 °C / @ 50° C at 50 Hz) 609 V – 820 V / 554 V – 820 V 2)3)
MPP voltage range (@ 25° C / @ 50° C at 60 Hz) 609 V – 820 V / 554 V – 820 V 2)3)
Rated input voltage 595 V
Max. input current 1400 A
Minimum input voltage / VMPP_min at IMPP < IDCmax 545 V / 545 V
Number of independent MPP inputs 1
Number of DC inputs 9 / 32 (Optiprotect)
Output (AC)
Rated power (@ 25 °C) / nominal AC power (@ 50 °C) 836 kVA / 760 kVA
Nominal AC voltage / range 342 V / 308 V – 376 V
AC frequency / range 50 Hz, 60 Hz / 47 Hz … 63 Hz
Rated frequency / rated voltage 50 Hz / 324 V
Max. output current 1411 A
Max. THD <3%
Power factor at rated power / adjustable shift factor 1 / 0.9 leading ... 0.9 lagging
Feed-in phases / connection phases 3 / 3
Efficiency 7)
Max. efficiency / European efficiency / CEC efficiency 98.6 % / 98.4 % / 98.5 %
Protection
Input side disconnection device Motor-driven switch-disconnector / circuit breaker (Optiprotect)
Output side disconnection device AC circuit breaker
DC overvoltage protection / AC overvoltage protection Surge arrester type I / surge arrester type I
Grid monitoring
Ground fault monitoring / Remote ground fault monitoring ○ / ○
Insulation monitoring
Surge arrester for auxiliary supply
Protection class (as per IEC 62103) / overvoltage category (as per IEC 60664-1) I / III
General Data
Dimensions (W / H / D) 2562 / 2279 / 956 mm (101 / 90 / 38 inch)
Weight 1800 kg
Operating temperature range -20 °C … +50 °C
Noise emission 5) 60 db(A)
Max. self-consumption (in operation) / self-consumption (at night) 1700 W4) / < 100
External auxiliary supply voltage 230 / 400 V (3 / N / PE)
Cooling concept OptiCool
Degree of protection: electronics / connection area (as per IEC 60529) IP54 / IP23
Application Unprotected outdoors
Maximum permissible value for relative humidity (non-condensing) 15 % … 95 %
Maximum operating altitude above MSL 2000 m
Fresh air consumption 3000 m³/h
Features
DC terminal Ring terminal lug / cage terminal
(Optiprotect)
AC terminal Ring terminal lug
Display
Communication protocols Ethernet (optical fiber optional), madbus
Sunny String-Monitor RS485 / is not required (Optiprotect)
Color of enclosure, door, base, roof RAL 9016 / 9016 / 7005 / 7004
Certificates and approvals (more upon request) EN 61000-6-2, EN 61000-6-4, EEG conformity, Arrêté du 4/23/08,
R.D. 1663 / 2000, R.D. 661 / 2007, BDEW-MSRL / FGW / TR86)
Classification of the ambient conditions (according to IEC 60721-3-4) 4S2, 4C2
● Standard features ○ Optional features — Not available
Type designation SC 760CP-10